Influence of the representation of the distribution transformer core configuration on voltages developed during unbalanced operations

The object of this paper is to emphasize the importance of the representation of the core configuration when seeking transients developed in a distribution transformer under an unbalanced situation. Digital time-domain simulations are performed with the Alternative Transients Program (ATP) for the c...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autores principales: Vernieri, Julieta Z., Barbieri, María Beatriz, Arnera, Patricia Liliana
Formato: Objeto de conferencia
Lenguaje:Inglés
Publicado: 2001
Materias:
ATP
Acceso en línea:http://sedici.unlp.edu.ar/handle/10915/36854
Aporte de:
Descripción
Sumario:The object of this paper is to emphasize the importance of the representation of the core configuration when seeking transients developed in a distribution transformer under an unbalanced situation. Digital time-domain simulations are performed with the Alternative Transients Program (ATP) for the case of a distribution three-phase transformer using the following two core configuration representations available in the ATP: three-legged core form and fivelegged core. Severe overvoltages and high saturated currents would not be evidenced if the wrong core configuration representation was used during simulations.